Edwards SIGA-SD Duct Smoke Detector
| Brand | Edwards |
|---|---|
| SKU | SIGA-SD |
| Type | Duct Detectors |
| Variants | 1 |
Edwards SIGA-SD (also searched as SIGA SD) is an intelligent SuperDuct Signature Series duct smoke detector that samples HVAC airflow and reports as an addressable device on a Signature loop.
A Signature Series photoelectric sensor is built into every SIGA-SD. It compares analog readings from the smoke sensing elements against historical readings and time patterns to make an alarm decision, and digital filters remove signal patterns that are not typical of fires. Differential sensing keeps gradual environmental change from triggering unwanted alarms: a rapid change such as smoke causes an alarm, while dust accumulating over time does not shift alarm sensitivity. Air enters the sensing chamber through a sampling tube that extends into the duct and returns through an exhaust tube. The assembly is less than 2 in deep, uses removable dust filters and conformally coated circuit boards, and comes apart for cleaning. The exhaust tube is included; the sampling tube is a separate order sized to the duct.
Specifications
| Detection | Photoelectric (light scattering) |
| Sensitivity | 0.79 to 2.46 %/ft obscuration |
| Air velocity | 100 to 4,000 ft/min |
| Air pressure differential | 0.005 to 1.00 inches of water |
| Operating voltage | 15.2 to 19.95 VDC |
| Current | Standby 45 µA; alarm 45 µA; standalone alarm 18 mA |
| Common alarm relay | One Form C, 2.0 A at 30 VDC (resistive) |
| Operating temperature (UL) | -20 to 158°F (-29 to 70°C) |
| Humidity | 10% to 93%, noncondensing |
| Dimensions | 8.70 x 5.45 x 1.90 in |
| Wire size | 14 to 22 AWG |
| Ship weight | 2.4 lb |
| Approvals | UL, ULC, CSFM, FM, MEA |
Installation notes
- Sampling tube ordered separately: size it to the duct from the SD-T8, SD-T18, SD-T24, SD-T36, SD-T42, SD-T60, SD-T78 or SD-T120 range.
- Tube orientation: install sampling tubes with the inlet holes facing the airstream; they rotate in 45-degree increments.
- Verify the duct first: Edwards directs that duct air velocity, temperature and humidity be tested before installation. The SD-VTK air velocity test kit is made for this.
- One remote device only: connect no more than one remote test station or LED indicator, with a maximum of 10 ohms per wire.
- High humidity: use the SD-PH protective housing to prevent condensation.
- Limits: a duct detector is not a substitute for open-area smoke detection or for a building's regular fire detection system.
Related models
- SD-TRM and SD-TRK: remote test/reset stations, magnet or key operated
- SIGA-LED: remote alarm LED
- SIGA-SDPCB: replacement PCB and Signature sensor kit for an installed SuperDuct housing
Specifications are taken from the Edwards data sheet E85001-0584. Manufacturer specifications are subject to change without notice.
Documents
FAQ
Is the sampling tube included?
No. The sampling tube is ordered separately and sized to the duct width; the exhaust tube is supplied with the detector.
What air velocity range does the SIGA-SD cover?
100 to 4,000 ft/min.
Does it have an auxiliary relay?
Yes. One Form C auxiliary alarm relay for controlling ancillary equipment, rated 2.0 A at 30 VDC.
Which systems is it used with?
It is a Signature Series addressable device for Edwards Signature loops, and it is compatible with the SIGA-LED remote alarm LED.
Questions about this product
Is Edwards SIGA-SD Duct Smoke Detector in stock?
Yes — 47 units are available and ready to ship from our US warehouse.
How fast will Edwards SIGA-SD Duct Smoke Detector ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does Edwards SIGA-SD Duct Smoke Detector ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.