Skip to content

Free shipping on orders over $99.

8:30 to 5 ET(704) 555-0142
Not sure what you have? Send the part number(704) 555-0142
Notifier Notifier NC-100R Addressable Relay Module view 1

Notifier NC-100R Addressable Relay Module

Notifier
$12.19
In stock — 48 available
In stock · ready to ship
Ships today — order before 3:00 PM ET
Delivery in 3–5 business days
Ships from the USA — free shipping over $99
BrandNotifier
SKUNC-100R
TypeRelay Modules
Variants1

Notifier NC-100R is an addressable relay module that provides two Form-C dry contacts that switch together. It is intended for addressable, two-wire systems, where the control panel switches the discrete contacts by code command.

According to the manufacturer's data sheet, the NC-100R(A) relay module is made for Notifier FireWarden Series intelligent control panels. The relay provides two isolated sets of Form-C dry contacts, so one command operates both sets at once.

Specifications

Contacts Two isolated sets of Form-C dry contacts, switched together
Addresses 01 to 99 with the FireWarden-100-2(C); 01 to 50 with the FireWarden-50(C)
Operating voltage 15 to 32 VDC
Maximum SLC current 6.5 mA with LED on
Contact rating, resistive, non-coded 3.0 A at 30 VDC; 0.9 A at 110 VDC; 0.9 A at 125 VAC
Contact rating, resistive, coded 2.0 A at 30 VDC
Dimensions 4.5 in high x 4 in wide x 1.25 in deep
Mounting 4 in square box, 2.125 in deep; optional SMB500 surface-mount back box
Operating temperature 32°F to 120°F (0°C to 49°C)
Humidity 10% to 93%, non-condensing

Application notes

  • Use the NC-100R when the panel needs to switch equipment contacts, not monitor them. For monitoring a normally-open contact, a monitor module is the right device.
  • Check the contact rating against the load, including whether the circuit is coded or non-coded, before wiring.
  • Confirm panel compatibility before ordering. The data sheet describes the module for FireWarden Series panels.

Specifications are taken from the Notifier data sheet for the NC-100R(A) relay module. Manufacturer specifications are subject to change without notice.

Documents

FAQ

Which panels is the NC-100R for?
Notifier FireWarden Series intelligent control panels: addresses 01–99 on the FireWarden-100-2(C) and 01–50 on the FireWarden-50(C).

What can it control?
Its two Form-C dry contacts can operate door holders, air handling unit shutdown and similar equipment, and can reset four-wire smoke detector power.

How is it mounted?
It mounts to a 4 in. square box 2.125 in. deep; the SMB500 is the optional surface-mount backbox.

Does it need an end-of-line resistor?
No. The data sheet lists EOL resistance as not used; the relay and circuitry are powered directly from the two-wire SLC.

Questions about this product

Is Notifier NC-100R Addressable Relay Module in stock?

Yes — 48 units are available and ready to ship from our US warehouse.

How fast will Notifier NC-100R Addressable Relay Module ship?

Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.

Where does Notifier NC-100R Addressable Relay Module ship from?

It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.