Notifier NC-100R Addressable Relay Module
| Brand | Notifier |
|---|---|
| SKU | NC-100R |
| Type | Relay Modules |
| Variants | 1 |
Notifier NC-100R is an addressable relay module that provides two Form-C dry contacts that switch together. It is intended for addressable, two-wire systems, where the control panel switches the discrete contacts by code command.
According to the manufacturer's data sheet, the NC-100R(A) relay module is made for Notifier FireWarden Series intelligent control panels. The relay provides two isolated sets of Form-C dry contacts, so one command operates both sets at once.
Specifications
| Contacts | Two isolated sets of Form-C dry contacts, switched together |
| Addresses | 01 to 99 with the FireWarden-100-2(C); 01 to 50 with the FireWarden-50(C) |
| Operating voltage | 15 to 32 VDC |
| Maximum SLC current | 6.5 mA with LED on |
| Contact rating, resistive, non-coded | 3.0 A at 30 VDC; 0.9 A at 110 VDC; 0.9 A at 125 VAC |
| Contact rating, resistive, coded | 2.0 A at 30 VDC |
| Dimensions | 4.5 in high x 4 in wide x 1.25 in deep |
| Mounting | 4 in square box, 2.125 in deep; optional SMB500 surface-mount back box |
| Operating temperature | 32°F to 120°F (0°C to 49°C) |
| Humidity | 10% to 93%, non-condensing |
Application notes
- Use the NC-100R when the panel needs to switch equipment contacts, not monitor them. For monitoring a normally-open contact, a monitor module is the right device.
- Check the contact rating against the load, including whether the circuit is coded or non-coded, before wiring.
- Confirm panel compatibility before ordering. The data sheet describes the module for FireWarden Series panels.
Specifications are taken from the Notifier data sheet for the NC-100R(A) relay module. Manufacturer specifications are subject to change without notice.
Documents
FAQ
Which panels is the NC-100R for?
Notifier FireWarden Series intelligent control panels: addresses 01–99 on the FireWarden-100-2(C) and 01–50 on the FireWarden-50(C).
What can it control?
Its two Form-C dry contacts can operate door holders, air handling unit shutdown and similar equipment, and can reset four-wire smoke detector power.
How is it mounted?
It mounts to a 4 in. square box 2.125 in. deep; the SMB500 is the optional surface-mount backbox.
Does it need an end-of-line resistor?
No. The data sheet lists EOL resistance as not used; the relay and circuitry are powered directly from the two-wire SLC.
Questions about this product
Is Notifier NC-100R Addressable Relay Module in stock?
Yes — 48 units are available and ready to ship from our US warehouse.
How fast will Notifier NC-100R Addressable Relay Module ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does Notifier NC-100R Addressable Relay Module ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.