Potter PAD100-MIM Micro Input Module
| Brand | Potter |
|---|---|
| SKU | PAD100-MIM |
| Type | Monitor Modules |
| Variants | 1 |
Potter PAD100-MIM — addressable micro input module that monitors initiating devices with a normally open set of dry contacts, for Potter IPA and AFC/ARC series addressable fire alarm control panels.
The PAD100-MIM is small enough to fit in the electrical box or enclosure behind the device it monitors, which makes it the usual choice for pull stations. It is enclosed in a plastic case to protect against shorts and ground faults and mounts with a single screw. A status LED flashes when the module is polled and flashes at a fast rate when the input is active.
Specifications
| Model | PAD100-MIM |
| Protocol | PAD addressable protocol |
| Input | One Class B dry contact input (normally open) |
| SLC wiring | Class A, Class X or Class B |
| Operating voltage | 24.0 V |
| SLC current | 200 µA standby and alarm |
| EOL resistor | 5.1K ohm |
| IDC wiring limits | 100 ohm maximum, 1 µF maximum |
| Modules per loop | 127 maximum |
| Dimensions | 1.75 x 1.36 x 0.43 in. |
| Connections | 6 in. pigtail leads |
| Operating environment | 32–120°F (0–49°C), 0–93% RH non-condensing |
Installation notes
- Address 1 to 127 is set with the seven-position DIP switch on the front of the module
- Mount in a 2-1/2 in. deep single-gang box, typically behind the monitored device
- Remove power and check field wiring for opens and shorts before connecting to the SLC
- UUKL certified for smoke control; 5 year warranty
Related models
- PAD100-SIM: single input module
- PAD100-DIM: dual input module
- PAD100-RM: relay module
Documents
FAQ
Which panels support the PAD100-MIM?
It is compatible with Potter IPA and AFC/ARC series addressable fire alarm control panels, and only with systems that use the PAD addressable protocol.
How is it addressed?
With the seven-position DIP switch on the front of the module, for addresses 1 to 127.
What end-of-line resistor does the input need?
A 5.1K ohm EOL resistor on the Class B input circuit.
Where is it mounted?
In a 2-1/2 in. deep single-gang box, usually in the box or enclosure behind the pull station or device it monitors.
Questions about this product
Is Potter PAD100-MIM Micro Input Module in stock?
Yes — 13 units are available and ready to ship from our US warehouse.
How fast will Potter PAD100-MIM Micro Input Module ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does Potter PAD100-MIM Micro Input Module ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.